Gašper Leskovec: Jožef Stefan Institute, Ljubljana, Slovenia · Costas Mylonas: UBITECH, Athens, Greece · Klemen Kenda: Jožef Stefan Institute, Ljubljana, Slovenia
Active learning (AL) can reduce the number of expensive N-1 contingency simulations needed to train data-driven power grid security classifiers, but the reported gains come almost entirely from offline studies on a static pool of pre-computed operating points, with no human in the loop. This paper reports the integration of an AL-based security assessment service into an operational digital twin platform, describing the deployed architecture, the dashboard–backend interface contract, and the resulting workflow: day-ahead candidates are ranked by informativeness, the operator selects which of them justify simulation, and the labels are produced by the digital twin rather than by the human. The loop has so far been exercised manually — 31 retraining runs and 91 ranking calls over twelve distinct day-ahead sets, with no scheduled operation — so what we report is system behaviour and not label efficiency. Under a temporal split, aggregate discrimination is nearly unchanged while recall on the insecure class falls by ten points at the fixed decision threshold; the three uncertainty-based query strategies coincide in the binary setting, so an interface offering four options realises two behaviours; and the top of the ranking reorders under retraining that leaves the reported model quality unchanged.
Keywords: active learning, human-in-the-loop, digital twin, power grid security assessment, N-1 criterion, system integration